Together we build.
siklasicher.
Fixings and Fastenings

Drop-In Anchor AN ES

Application

Drop-In Anchor for single fixing in non-cracked concrete and multiple fixing in cracked concrete. Suitable for fixing pipelines, channels, etc. meeting the respective approval requirements. The anchor must only be used for dry interiors. For damp locations and outdoor constructions the stainless steel version is required.

  • No special drill required
  • Setting tool for distance-controlled forced expansion
  • Suitable for push-through mounting

Installation

As expansion tool use the respective Setting Tool for Drop-In Anchor or the Plug-on Setting Tool ASW. The "intelligent" expansion cone facilitates the mounting with bore dia. tolerances or varying concrete quality. By the controlled deformation of the cone during installation, the needed edge and centre distances are decreasing considerably.

Technical Data

Single fixing:
Extract from application conditions of ETA-10/0257
Permissible loads according to EN 1992-4 without influence of centre and edge distances. Overall safety factor is taken into account ( YM und YF ).

Anchor size
M8x30*
M8x40
M10x30
M10x40
M12x50
M16
Nominal diameter of drill d0 = [mm] 10 10 12 12 15 20
Depth of bore hole h0 = [mm] 30 40 30 40 50 65
Installation torque Tinst = [Nm] 8 8 15 15 35 60
Diameter of clearance hole in the connecting
element df ≤ [mm]
9 9 12 12 14 18
Thread length Lth [mm] 13 20 12 15 18 23
Min. screwing depth Lsdmin [mm] 9 9 10 11 13 18
Min. thickness of concrete slab hmin [mm] 100 100 120 120 130 160
Min. centre distance smin [mm] 60 80 100 100 120 150
Min. edge distance cmin [mm] 95 95 115 135 165 200
      
Perm. tensile load in non-cracked concrete
(Screw 5.6 up to 8.8)
     
C20/25 [kN] 3.2 3.6 3.2 4.9 6.9 10,2
C25/30 [kN] 3.6 3.8 3.6 5.5 7.7 11.4
C30/37 [kN] 3.9 4 3.9 6.0 8.5 12.5
C40/50 [kN] 4.5 4.4 4.5 7.0 9.8 14.5
C50/60 [kN] 5.1 4.7 5.1 7.8 10.9 16.2
Lateral load (Screw 5.6) ≥ C20/25 zul. V [kN] 3.8 3.9 3.8 4.1 9 16.8
Lateral load (Screw 5.8) ≥ C20/25 zul. V [kN] 3.8 3.9 3.8 4.1 11.1 18
Lateral load (Screw 8.8) ≥ C20/25 zul. V [kN] 3.8 3.9 3.8 4.1 11.1 18
Perm. bending moment (Screw 5.6) Mzul [Nm] 8.1 8.1 15.8 15.8 27.8 71
Perm. bending moment (Screw 5.8) Mzul [Nm] 10.9 10.9 21.1 21.1 37.1 94.9
Perm. bending moment (Screw 8.8) Mzul [Nm] 17.1 17.1 33.7 34.3 60 152
Charact. centre distance scr [mm] 90 120 90 120 150 195
Charact. edge distance ccr [mm] 45 60 45 60 75 97,5
      
Loads under fire exposure steel ≥ 5.6      
Perm. load R30 perm. F [kN] 0.9 1.8 0.9 1.8 3.2 4.7
Perm. load R60 perm. F [kN] 0.9 1.3 0.9 1.8 3.1 4.7
Perm. load R90 perm. F [kN] 0.8 0.8 0.9 1.2 1.8 3.3
Perm. load R120 perm. F [kN] 0.5 0.5 0.7 0.8 1.2 2.2

* Application for indeterminated static systems

Multiple fixing:
Extract from application conditions of ETA-10/0258
For the multiple use for non-structural applications. Permissible loads according to EN 1992-4 without influence of centre and edge distances. The overall safety factor is taken into account ( YM und YF ).
The maximum permissible load per fixing point may be less than the permissible load of the anchor, depending on national regulations.

Anchor size
M8x25
M8x30
M8x40
Nominal diameter of drill d0 = [mm] 10 10 10
Depth of bore hole h0 = [mm] 25 30 40
Installation torque Tinst = [Nm] 8 8 8
Diameter of clearance hole in the connecting
element df ≤ [mm]
9 9 9
Thread length Lth [mm] 12 13 20
Min. screw depth Lsdmin [mm] 8 9 9
Standard/Min. thickness of component
hmin1 / hmin2 [mm]
100/80 100 100
Min. centre distance smin [mm] 50 60 80
Min. edge distance cmin [mm] 100 95 95
   
Perm. tensile load cracked/non-cracked concrete   
C12/15 and C16/20 [kN] 1.2 - -
C20/25 to C50/60 [kN] 1.9 1.7 2
Perm. bending moment (Steel 4.6) Mzul [Nm] 6.4 6.4 6.4
Perm. bending moment (Steel 5.6) Mzul [Nm] 8.1 8.1 8.1
Perm. bending moment (Steel 5.8) Mzul [Nm] 10.9 10.9 10.9
Perm. bending moment (Steel 8.8) Mzul [Nm] 17.1 17.1 17.1
Charact. centre distance scr [mm] 75 180 210
Charact. edge distance ccr [mm] 38 90 105
   
Loads under fire exposure screw ≥ 4.8   
Perm. load R30 perm.. F [kN] 0.6 0.9 1.1
Perm. load R60 perm. F [kN] 0.6 0.9 0.9
Perm. load R90 perm. F [kN] 0.6 0.6 0.6
Perm. load R120 perm. F [kN] 0.5 0.5 0.5
Loads under fire exposure screw ≥ 5.6   
Perm. load R30 perm. F [kN] 0.6 0.9 1.5
Perm. load R60 perm. F [kN] 0.6 0.9 1.5
Perm. load R90 perm. F [kN] 0.6 0.9 0.9
Perm. load R120 perm. F [kN] 0.5 0.5 0.5
Charact. centre distance scr,fi [mm] 100 180 210
Charact. edge distance ccr, fi [mm] 50 90 105

Anchor size
M10x25
M10x30
M10x40
M12x25
M12x50
M16
Nominal diameter of drill d0 = [mm] 12 12 12 15 15 20
Depth of bore hole h0 = [mm] 25 30 40 25 50 65
Installation torque Tinst = [Nm] 15 15 15 35 35 60
Diameter of clearance hole in the connecting
element df ≤ [mm]
12 12 12 14 14 18
Thread length Lth [mm] 12 12 15 12 18 23
Min. screw depth Lsdmin [mm] 10 10 11 12 13 18
Standard/Min. thickness of component
hmin1 / hmin2 [mm]
100/80 120 120 100/80 130 160
Min. centre distance smin [mm] 60 100 100 100 120 150
Min. edge distance cmin [mm] 100 115 135 110 165 200
      
Perm. tensile load cracked/non-cracked concrete      
C12/15 and C16/20 [kN] 1.7 - - 1.7 - -
C20/25 to C50/60 [kN] 2.1 2 2 2.1 2.4 6.3
perm. bending moment (Steel 4.6) Mzul [Nm] 12.8 12.8 12.8 22.2 22.2 56.9
perm. bending moment (Steel 5.6) Mzul [Nm] 15.8 15.8 15.8 27.8 27.8 71
perm. bending moment (Steel 5.8) Mzul [Nm] 21.1 21.1 21.1 37.1 37.1 94.9
perm. bending moment (Steel 8.8) Mzul [Nm] 34.3 33.7 34.3 60 60 152
Charact. centre distance scr [mm] 75 230 170 75 170 400
Charact. edge distance ccr [mm] 38 115 85 38 85 200
      
Loads under fire exposure ≥ 4.8      
Perm. load R30 perm. F [kN] 0.6 0.9 1.5 0.6 1.5 4
Perm. load R60 perm. F [kN] 0.6 0.9 1.5 0.6 1.5 4
Perm. load R90 perm. F [kN] 0.6 0.9 1.1 0.6 1.5 3
Perm. load R120 perm. F [kN] 0.5 0.7 0.9 0.5 1.2 2.4
Loads under fire exposure screw ≥ 5.6      
Perm. load R30 perm. F [kN] 0.6 0.9 1.5 0.6 1.5 4
Perm. load R60 perm. F [kN] 0.6 0.9 1.5 0.6 1.5 4
Perm. load R90 perm. F [kN] 0.6 0.9 1.5 0.6 1.5 3.7
Perm. load R120 perm. F [kN] 0.5 0.7 1.0 0.5 1.2 2.4
Charact. centre distance scr,fi [mm] 100 170 170 100 200 400
Charact. edge distance ccr, fi [mm] 50 85 85 50 100 200


Valid are the values of the mentioned approval which can be seen on our website www.sikla.com/downloads.

Material:
Steel, galvanised

Approvals / Conformity

For the multiple use for non-structural applicatons Sikla approval ETA-10/0258 (M8 - M12), for installation in non-cracked concrete Sikla approval ETA-10/0257, fire protection testing, VdS-conform, FM-Approval ≥ M10

ETA 10/0257 PDF | 2.4 MB ETA 10/0258 PDF | 3.9 MB FM - Sikla Anchors AN PDF | 260.1 KB

1) Delivery date on request - goods are procured order-related.

TypeDrill hole ø x
depth [mm]
Thread ø x
length [mm]
W
[kg]
Quantity
[pack]
Part
number
ES M8 x 2510 x 25M8 x 120.01100 116618
ES M8 x 3010 x 30M8 x 130.01100 110467
ES M8 x 4010 x 40M8 x 200.01100 110468
ES M10 x 2512 x 25M10 x 120.0250 116619
ES M10 x 3012 x 30M10 x 120.0250 110506
ES M10 x 4012 x 40M10 x 150.0250 110469
ES M12 x 25 1)15 x 25M12 x 120.0250 116620
ES M12 x 5015 x 50M12 x 180.0450 110470
ES M16 x 6520 x 65M16 x 230.1025 110471